Water Feeder Automatic Reset 24 VAC VXT24 for Steam Boilers
Sign In for price In Stock
QUANTITY
Same Day Shipping on orders placed by 4pm EST
Product Overview
The new VXT is the first automatic steam boiler water feeder designed to monitor the amount of water added to a steam boiler. The addition of make-up water raises the oxygen level in a boiler and accumulates lime and other mineral deposits. Excessive boiler make-up water can cause cast iron boilers to rust internally, severely shortening the boiler's life. Mineral deposits from too much make-up water can impede heat transfer causing cast iron boiler sections to overheat and crack. Unlike other water feeders, the VXT can protect the life of a boiler by exposing system leaks that call for excessive make-up water - giving you the information you need to diagnose and repair the system before it's too late.
- Universal compatibility
- Programmable feed delay settings (30 sec to 10 Min)
- Programmable feed amount settings (LWCO and 1 - 5 gal)
- Manual feed button
- Underfeed protection
- Lock-out flood protection, electronic type
- Upon a feed signal from low water cut off, VXT feeder delays to allow condensate to return to boiler
- If make up water is required after the delay period the VXT will initiate a feed cycle
- Digital feed counter tracks all water fed into the boiler including water added using the manual feed button
Product Details
Brand | Hydrolevel |
---|---|
Product Type | Automatic Reset |
Part Number | VXT24 |
Voltage | 24VAC |
Used on | Steam Boilers |